NB-GPC Range

 

BACnet Advanced Application Controllers

The NB-GPC range of controllers offers complete stand-alone control as well as full peer-to-peer capabilities with other devices on the same physical BACnet network. GPC devices are fully programmable, networkable, expandable, and designed to provide hardware and software flexibility using onboard I/O and STATbus - AAM's innovative sensor networking technology.

Each controller complies with ANSI/ASRAE BACnet standards, and are BTL listed as BACnet Advanced Application Controllers (B-AAC).

Features

  • BACnet Schedules
    supports dynamic, flexible weekly and exception schedule control
  • Native BACnet Alarming
    define destinations to where object alarms and events are sent
  • PID Control Loops
    closed-loop analog control with flexible setpoint scheduling
  • Thermostatic Control Loops
    closed-loop, thermostatic (on/off) control with seasonal and schedule control
  • I/O Expansion
  • HAO Switch
  • Pulse Pair PID Control Loop
    closed-loop paired-output control with flexible setpoint scheduling
  • Embedded Logic Objects
    built-in object-based programming for advanced logic & calculations

Product Models

  NB-GPC1 NB-GPC2 NB-GPC4
Universal Inputs 12 8 12
Digital Inputs 1 1 1
Analog Outputs 6 4 6
Digital Outputs 6 5 6
STATbus Ports 3 1 3
SPL Regions 8 2 6
Staging Objects 4 2 6

Expansion Limits

  NB-GPC1 NB-GPC2 NB-GPC4
Universal Input 12 4 (STAT) 36
Digital Input 7 - 7
Analog Output 6 - 18
Digital Output 6 - 18

IOX Modules

  • SSB-IOX2-1 12 UI / 0 DI / 6 AO / 6 DO
  • SSB-DI1 1 Digital Input
  • SSB-DO2-I 2 Dry Contact Inputs / 2 Digital Inputs (relay)
  • SBC-STAT 1 Digital Temp and/or Humidity Input (STAT1-D, STAT2-D, STAT3, RH1, RH3, RHT)

Specifications

General Specifications
Processor high speed 32-bit processor
Terminations pluggable blocks for inputs, outputs, power, & network connection
Wiring 18-22 gauge wire
Baud Rates 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 (kbps)
Input Supply 22 to 29 VAC 50/60 Hz @ 4.16A max, PTC protection
Transformer internal isolated switching power supply
Indicators LEDs for line power, regulated DC voltages
Outputs analog: 0-10 VDC into 1k Ohm load or 0-20 mA into 250 Ohm load
digital: 6 to 30 VAC, 50/60 Hz @ 1A resistive or inductive digital outputs provide varsitor protection
Operating & Storage Conditions
Operating Temperature 32˚ F to 122˚ F (0˚ C to 50˚ C)
Operating Humidity 0 to 90% relative humidity non-condensing
Storage Temperature -40˚ to 151˚ F (-40˚ to 66˚ C)
Dimensions & Mounting
Dimensions NB-GPC1 8.2" x 6.5" x 1.0" in. / 1.4 lbs
NB-GPC2 6.9" x 5.7" x 1.0" in. / 1.0 lbs
NB-GPC4 8.2" x 6.5" x 1.0" in. / 1.4 lbs
Mounting flat surface with screws
Agency Approvals
Complies with CE directives and standards
FCC - Class B Computing Device; Part 15
UL Listed 916 - Management Equipment, Energy (PAZX)